Sauna heater sizing calculator

A sauna heater needs 1 kW for every 45 cubic feet of room: a 6 by 6 by 7 foot room (252 cubic feet) needs 5.6 kW, or 7.0 kW if its walls include concrete, tile or glass.

The standard sizing rule for traditional sauna heaters is 1 kW of heater power per 45 cubic feet of room volume. Rooms whose walls include concrete, tile, or glass need about 25 percent more, because those surfaces absorb heat. The calculator below handles your exact dimensions; a reference table of common room sizes follows it.

Once you have a kW figure, size the circuit for it with the sauna electrical requirements calculator, then see how much a sauna costs to run at that power.

Your heater power

Room volume
252 cu ft
Recommended heater power
5.6 kW

Nearest heater size sold here: 6 kW, sized for rooms of 225 to 270 cubic feet. Traditional saunas built with it: 1 person saunas (2), 2 person saunas (13), 3 person saunas (17), 4 person saunas (27), 5 person and larger saunas (11).

Compare heater power across the full sauna database, then confirm the final sizing with the heater manufacturer's own chart; models vary.

Common room sizes at a glance

Recommended heater power by sauna room dimensions (1 kW per 45 cubic feet)
Room (L x W x H)VolumeHeater powerWith concrete or glass walls
4 x 4 x 7 ft112 cu ft2.5 kW3.1 kW
4 x 6 x 7 ft168 cu ft3.7 kW4.7 kW
5 x 7 x 7 ft245 cu ft5.4 kW6.8 kW
6 x 6 x 7 ft252 cu ft5.6 kW7.0 kW
6 x 8 x 7 ft336 cu ft7.5 kW9.3 kW
8 x 8 x 7 ft448 cu ft10.0 kW12.4 kW

Sauna heater size chart

Heater power by room volume at 1 kW per 45 cubic feet, with the 25 percent allowance for concrete, tile or glass walls.

Sauna heater size by room volume (1 kW per 45 cubic feet)
Room volumeHeater powerWith concrete, tile or glass walls
100 cu ft2.2 kW2.8 kW
150 cu ft3.3 kW4.2 kW
200 cu ft4.4 kW5.6 kW
250 cu ft5.6 kW6.9 kW
300 cu ft6.7 kW8.3 kW
350 cu ft7.8 kW9.7 kW
400 cu ft8.9 kW11.1 kW
450 cu ft10.0 kW12.5 kW
500 cu ft11.1 kW13.9 kW

Heater sizing questions

What size heater does my room need?
One kW of heater power for every 45 cubic feet of room volume. A 6 by 6 by 7 foot room is 252 cubic feet, which comes out at 5.6 kW, so the nearest size sold is 6 kW. Enter your own dimensions above for the exact figure.
Do concrete, tile or glass walls change the answer?
Yes, by about 25 percent. Those surfaces absorb heat instead of holding it in the room, so the same 252 cubic foot room with a glass front works out at 7.0 kW rather than 5.6 kW. The checkbox in the calculator applies exactly that factor.
How much does ceiling height matter?
It is one of the three dimensions in the volume, so it counts fully. On a 6 by 6 foot footprint every extra foot of ceiling adds 36 cubic feet, which is another 0.8 kW of heater. That is why the rule is volume rather than floor area.
What happens if the heater is under the calculated size?
It has to run longer to reach its set temperature and, in cold weather, may not reach it at all. The rule sizes for the room you measured, not for a preference, and a heater above the figure costs more to buy and more to run without changing the temperature it settles at.
What comes after the kW figure?
The circuit. A heater is a continuous load, so code sizes the breaker and the wire at 125 percent of its draw, which puts a 6 kW heater at 240 volts on a 35 amp circuit with 8 AWG copper. The electrical requirements calculator works that out for any heater power.

Prices and specifications verified September 27, 2026, and re-checked weekly after that. How these numbers are checked.